Permit: T04CM00220

Parcel: 119031350


Addresses:

744 W 41ST ST

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
06/29/2004 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
06/17/2004 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) FOUNDATION FOOTING MUST BE 19" WIDE AND 12" BELOW NATURAL GRADE PRESENTLY 16" WIDE AND 7" BELOW GRADE 2) CLAY SEWER PIPE NOT ALLOWED UNDER BLDG-MUST BE REPLACED 3) 10' WATER TEST REQUIRED ON PLUMBING AFTER REPLACED 4) ALL PLUMBING THAT MAY CONTACT MUST BE WRAPPED OR SLEEVED 5) A TWO WAY CLEANOUT REQUIRED ON SEWER. PLEASE FOLLOW THE PLAN