Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/11/2004 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 03/10/2004 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 03/05/2004 |
FRAMING |
|
Denied |
IVRS - Inspection 0935*/ 1) NO POTABLE WATER TEST 2) NO DWV WATER TEST 3) LATH DAMAGED BEHIND WATER HEATER 4) ABRE CONDUCTORS CANNOT EXTEND ABOVE MAIN DISCONNECT IN PANEL-MAY SHORT OUT ON ? BAR 5) UFER GROUND CANNOT RUN 30 FEET THRU HOUSE. INSTALL 2 GROUND RODS AND REMOVE CONDUCTOR FROM INSIDE HOUSE 6) SHEAR WALL 9 NOT CLIPPED PER 10/DT1 6" ON CENTER 7) SUPPORT 1/2" GAS LINE AT 6 FEET ON CNETER 8) STOPPED INSPECTION, HOUSE NOT READY 9) 4TH FAILURE, REFEE |
| 03/04/2004 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) NO GAS TEST, NO WATER TEST 2) STOPPED INSPECTION 3) REFEE DUE |
| 03/03/2004 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) CANCEL |
| 03/01/2004 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) COMPLETE ALL TRADES 2) RECALL WHEN READY |