Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04CM00214
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/19/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*SENT TO TEP ON 02/18/04PM | |
02/17/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0250*/ 1) THE 2X4 DROP IN FIXTURES MUST BE SECURED TO THE CEILING GRID MAIN SUPPORTING TEES [MAIN RUNNER] WITH EITHER 4 CLIPS [PUNCHED INTO FIXTURE] OR 2 SCREWS SET INTO CENTERS - TWO ENDS. 2) THE CIRCUIT BREAKERS IN THE MAIN PANEL ARE ALL SET ON THE 'EVEN' SIDE OF THE PANEL. HOW WILL THE PANEL INDEX MATCH THE PLAN CIRCUITING? |