Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/19/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP ON 02/18/04PM |
| 02/17/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0250*/ 1) THE 2X4 DROP IN FIXTURES MUST BE SECURED TO THE CEILING GRID MAIN SUPPORTING TEES [MAIN RUNNER] WITH EITHER 4 CLIPS [PUNCHED INTO FIXTURE] OR 2 SCREWS SET INTO CENTERS - TWO ENDS. 2) THE CIRCUIT BREAKERS IN THE MAIN PANEL ARE ALL SET ON THE 'EVEN' SIDE OF THE PANEL. HOW WILL THE PANEL INDEX MATCH THE PLAN CIRCUITING? |