Permit: T04CM00202

Parcel: 138134010


Addresses:

408 W HAMMERHEAD WY

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
06/11/2004 PLUMBING - ROUGH, SOIL Approved
02/19/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*/ 1) PLUMBING IS NOT PER APPROVED PLAN BUT IS PER FIELD CHANGE. YOU MUST PROVIDE A COMPLETE REVISED PLUMBING PLAN BEFORE INTERMEDIATE INSPECTIONS OR PROJECT WILL BE STOPPED
02/17/2004 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*/ 1) PLUMBING IS NOT PER APPROVED PLAN-SEE ITEM 1 FROM 2/12/04 2) NEXT FAILURE WILL BE CHARGED A REINSPECTION FEE
02/13/2004 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection 0000*
02/12/2004 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*/ 1) PLUMBING IS NOT LAYED OUT PER APPROVED PLAN. BUILD TO PLAN OR REVISE PLAN TO AS BUILT. TUB DRAIN AND VENT NOT INSTALLED. 2ND FLOOR 2" DOWN WRONG LOCATION. SECOND FLOOR 3" STACK WRONG LOCATION 2) SEWER LINE BETWEEN CLEANOUTS AND HCS HAS MORE THAN 135 DEGREE HORIZONTAL CHANGE WITHOUT CLEAN OUTS 3) SECOND FLOOR CLEANOUTS LEAKING