Permit: T04CM00193

Parcel: 12701008A

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/17/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*/ OK FOR C OF O.
06/16/2004 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
06/15/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) FASTENERS CANNOT PENETRATE ANY PORTION OF THE GREASE DUCT. FLEX CONNECTOR MUST BE LISTED FOR USE ON A GREASE DUCT. PROVIDE LISTING. 2) EXTEND SEWER VENT 2' ABOVE EVAP COOLER. 3) FINISH CONNECTING ELEC. TO A/C UNITS. 4) PERM. LABEL ALL EQUIP. ON ROOF. 5) CONDENSOR NOT FUSED CORRECTLY. SECURE REFER LINES. 6) PAINT BLACK IRON ON ROOF.