Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T04CM00187
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/10/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*/ OK FOR FINAL C OF O. | |
05/06/2004 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :*/ NEED TO SEE INTERLOCK FAN AND MAKE-UP AIR. | |
05/05/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ WRONG ADDRESS LABELED ON EQUIPMENT. EXTEND 2 SEWER VENTS. NEED TO SEE EXHAUST FAN INTERLOCKED WITH EVAP COOLER. |
|
05/03/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*. DENIED. Extend water heater vent 3' above evap. cooler. Provide grease cups on exhaust fans. Provide outside air intakes on A/C units. Label unit data plates with proper heat strip installed and fuse accordingly. Permanently label equipment on roof with address and unit number. Extend sewer vents 3' above evap. coolers. Servicable equipment cannot be within 10' of the edge of the roof. |