Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T04CM00187

Parcel: 12613018A


Addresses:

4540 E BROADWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - HOOD SYSTEMS

Date Description Inspector Results Comments
04/12/2004 MECHANICAL - HOOD SYSTEMS Approved IVRS - Inspection 0000*
04/07/2004 MECHANICAL - HOOD SYSTEMS Denied IVRS - Inspection 0999*/ FIRE WRAP NOT INSTALLED PER MANUFACTURERS SPECS. BANDING MUST BE WITHIN 1½" FROM EDGES AND SPACED 10½" APART. WRAP MUST EXTEND ALL THE WAY TO TOP OF GREASE DUCT. PROVIDE MIN. 3" OVERLAP ON JOINTS AND SEAMS. DO NOT TAPE JOINTS AND SEAMS - CANNOT VERIFY PROPER OVERLAP. PLEASE PROVIDE INSTALLATION INSTRUCTIONS.