Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOOD SYSTEMS
Permit Number - T04CM00187
Inspection Description - MECHANICAL - HOOD SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/12/2004 | MECHANICAL - HOOD SYSTEMS | Approved | IVRS - Inspection 0000* | |
04/07/2004 | MECHANICAL - HOOD SYSTEMS | Denied | IVRS - Inspection 0999*/ FIRE WRAP NOT INSTALLED PER MANUFACTURERS SPECS. BANDING MUST BE WITHIN 1½" FROM EDGES AND SPACED 10½" APART. WRAP MUST EXTEND ALL THE WAY TO TOP OF GREASE DUCT. PROVIDE MIN. 3" OVERLAP ON JOINTS AND SEAMS. DO NOT TAPE JOINTS AND SEAMS - CANNOT VERIFY PROPER OVERLAP. PLEASE PROVIDE INSTALLATION INSTRUCTIONS. |