Inspection Status: Approved
Inspection History: MECHANICAL - HOOD SYSTEMS
| Date |
Description |
Inspector |
Results |
Comments |
| 04/12/2004 |
MECHANICAL - HOOD SYSTEMS |
|
Approved |
IVRS - Inspection 0000* |
| 04/07/2004 |
MECHANICAL - HOOD SYSTEMS |
|
Denied |
IVRS - Inspection 0999*/ FIRE WRAP NOT INSTALLED PER MANUFACTURERS SPECS. BANDING MUST BE WITHIN 1½" FROM EDGES AND SPACED 10½" APART. WRAP MUST EXTEND ALL THE WAY TO TOP OF GREASE DUCT. PROVIDE MIN. 3" OVERLAP ON JOINTS AND SEAMS. DO NOT TAPE JOINTS AND SEAMS - CANNOT VERIFY PROPER OVERLAP. PLEASE PROVIDE INSTALLATION INSTRUCTIONS. |