Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T04CM00146

Parcel: 133552300


Addresses:

9565 E 22ND ST #105


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T04CM00146

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/30/2004 MECHANICAL - FINAL Approved IVRS - Inspection :
See detailed listing on site.| 999*
04/29/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) PROVIDE ELEC CIRCUITS AND DISCONNECTS FOR WALK-IN COOLER CONDENSORS. 2) MARK UNIT DATA PLATE WITH PROPER HEAT STRIP INSTALLED AND FUSE ACCORDINGLY. 3) PROVIDE AN OUTSIDE AIR INTAKE. 4) SECURE SEAL TITE CONDUIT TO A/C UNIT. 5) PERMANENTLY LABEL A/C UNIT WITH SUITE NUMBER.
04/26/2004 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :
See detailed listing on site.| 999*/ 1) OK FOR TEMP C OF O
04/23/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ EQUIPMENT ON ROOF NOT READY FOR INSP. PROVIDE ROOF JACKS ON ALL ROOF PENETRATIONS. PROVIDE DISCONNECTING MEANS FOR CONDENSORS.