Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T04CM00146
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/30/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection : See detailed listing on site.| 999* |
|
04/29/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) PROVIDE ELEC CIRCUITS AND DISCONNECTS FOR WALK-IN COOLER CONDENSORS. 2) MARK UNIT DATA PLATE WITH PROPER HEAT STRIP INSTALLED AND FUSE ACCORDINGLY. 3) PROVIDE AN OUTSIDE AIR INTAKE. 4) SECURE SEAL TITE CONDUIT TO A/C UNIT. 5) PERMANENTLY LABEL A/C UNIT WITH SUITE NUMBER. |
|
04/26/2004 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection : See detailed listing on site.| 999*/ 1) OK FOR TEMP C OF O |
|
04/23/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ EQUIPMENT ON ROOF NOT READY FOR INSP. PROVIDE ROOF JACKS ON ALL ROOF PENETRATIONS. PROVIDE DISCONNECTING MEANS FOR CONDENSORS. |