Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/07/2004 | ELECTRIC - ABOVE CEILING | Approved | ||
| 04/29/2004 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/23/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 04/19/2004 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0999*/ RECESSED FIXTURES TO BE POSITIVLY ATTACHED TO THE CEILING GRID VIA BRACKETS OR OTHER APPROVED. M.C. CABLE TO BE SUPPORTED WITHIN 12" OF JUNCTION BOX AND 6' THEREAFTER. M.C. CABLE NOT TO LAY ONTO CEILING TILE. | |
| 04/01/2004 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0999* |