Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T04CM00133
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/28/2004 | MECHANICAL - INTERMEDIATE | Approved | ||
| 04/22/2004 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) NEED TO SEE EXHAUST FAN AND DUCT IN LOUNGE AND SPACE HEATER IN WAREHOUSE 2) ON FINAL HAVE CEILING TILES REMOVED AND DUCT SMOKE DETECTORS POWERED AND OPERATIONAL WITH CLEAR ACCESS 3) DO NOT OPERATE A/C EQUIPMENT UNTIL DUCT SMOKE DETECTORS HAVE BEEN INSPECTED | |
| 04/15/2004 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ OK TO STOCK SHELVES IN MAIN SALES FLOOR AREA. | |
| 03/24/2004 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* | |
| 03/19/2004 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) INSPECTED ROUGH DUCT, FLEX AND DIFFUSERS IN MAIN SALES FLOOR. OK FOR CEILING TILES. LEAVE OUT UNDER EACH DUCT SMOKE DETECTOR. INSPECTED CONDENSATE DRAIN LINES IN MAIN SALES FLOOR AREA |