Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T04CM00130
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/01/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
| 02/20/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*/ 1) CONDENSATE DRAINS CANNOT TERMINATE ONTO A SIDEWALK. RELOCATE TO AN APPROVED AREA OF DISPOSAL. PAINT EXPOSED PVC WITH LATEX PAINT. BLOCK EVERY 4'. 2) PROVIDE SCREENS IN EXHAUST T-TOPS. SUPPORT EXHAUST FLEX DUCT IN ATTIC. 3) GAS FLEX CONNECTORS CANNOT EXCEED 3' IN LENGTH. 4) PERMANENTLY LABEL A/C UNITS WITH ADDRESS AND UNIT NUMBERS.. 5) ADJUST OUTSIDE AIR INTAKE AS PER PLAN. |