Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/11/2004 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000* |
| 03/04/2004 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
1) OVERSPAN GARAGE WALL AT FRONT ENTRY 2) ROOF TO WET TO WALK (RAINING) 3) OVERSPANS FRONT OF HOUSE 4) BATHROOM WALL WEST SIDE-NOT COMPLETELY FRAMED 5) SHIM 3 POINT BEARING TRUSSES 6) CHECK ENTIRE HOUSE FOR OVERSPANS |
| 03/02/2004 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/ 1) PROVIDE BLOCK UNDER PONY WALLS PER PLAN 2) GABLE END BRACING NOT PER PLAN 3) SHEAR TRANSFER AT ENTRY NOT PER PLAN 5/SD3 SEE 16/SD3 FOR ENTRY REQUIRES P-1 SHEAR 4) NAIL PERIMETER BLOCKS |