Permit: T04CM00114

Parcel: 138042150


Addresses:

602 W CALLE CASTILE

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE RELOCATION

Date Description Inspector Results Comments
04/28/2004 ELECTRIC - SERVICE RELOCATION Approved IVRS - Inspection :*
04/27/2004 ELECTRIC - SERVICE RELOCATION Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) TWO 8 FEET GROUND RODS REQUIRED TO BE INSTALLED AT LEAST 6 FEET APART. CONNECTED TO THE ELECTRIC SERVICE PANEL WITH A CONTINOUS #4 SOLID CONDUCTOR 2) PUT ADDRESS ON PANEL. MAGIC MARKER OK. USE ACORN CLAMPS ON GROUND RODS