Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/28/2004 | ELECTRIC - SERVICE RELOCATION | Approved | IVRS - Inspection :* | |
| 04/27/2004 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) TWO 8 FEET GROUND RODS REQUIRED TO BE INSTALLED AT LEAST 6 FEET APART. CONNECTED TO THE ELECTRIC SERVICE PANEL WITH A CONTINOUS #4 SOLID CONDUCTOR 2) PUT ADDRESS ON PANEL. MAGIC MARKER OK. USE ACORN CLAMPS ON GROUND RODS |