Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T04CM00106
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/22/2004 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :*/ 1) WATER TEST THRU ROOF WASTE AND VENT OK 2) H20 TEST ON H20 PIPING OK | |
| 07/22/2004 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection :I AM UNABLE TO MAKE THIS INSP AT 1:30PM DUE TO HEAVY WORKLOAD PLEASE RECALL | |
| 07/16/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*/ 1) WATER TEST THRU ROOF ON WASTE AND VENT IS REQUIRED 2) SEE INSPECTION DATED 7/12/04 FOR OTHER COMMENTS 3) DRAINAGE FOR LAV TO BE 1 1/2" FROM BARREL OF FITTING TO FIXTURE NOT TO EXCEED 42" | |
| 07/12/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*/ 1) INSTALL PER APPROVED PLAN ON H20 PIPING AND WASTE AND VENT OR PROVIDE CITY APPROVED REVISED PLAN ON SITE OF YOUR INSTALLATION 2) ALL PIPING TO BE SUPPORTED WITH APPROVED METHODS AND MATERIALS 3) H20 PIPING TO HAVE HOT AND COLD SEPERATION PER INSTALLATION INSTRUCTIONS 4) PROVIDE PRESSURE TEST ON H20 PIPING WITH GAUGE | |
| 07/09/2004 | PLUMBING - INTERMEDIATE | Cancelled | IVRS - Ri canceled |