Inspection History Details
Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
Permit Number - T04CM00106
Inspection Description - EXCAVATION/LAYOUT REBAR & ZON
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/01/2004 | EXCAVATION/LAYOUT REBAR & ZON | Approved | IVRS - Inspection :* | |
| 05/14/2004 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) BOTTOM OF FOOTING TO BE 12" MINIMUM BELOW NATURAL GRADE REF SECTION A-A PAGE 10 2) CLEANOUT ALL LOOSE DEBRIS FROM FOOTINGS AND MOVE TAILINGS AWAY FROM EDGE OF FOOTING OR RESTRAIN THEM SO THEY WON'T FALL BACK IN 3) 2 #4 REBAR NEED TO BE CONTINOUS (REF SECTION A-A) THAT MEANS CORNER BEDNS AND PROPER LAP SPLICES 4) REBAR MUST BE 3" CLEAR FROM EARTH. PLEASE SEE DETAIL PP 10 5) PLEASE PROVIDE CONTRACTORS NAME AND PHONE NUMBER FOR THIS PROJECT (GENERAL CONTRACTOR) |
|
| 05/12/2004 | EXCAVATION/LAYOUT REBAR & ZON | Not ready for Inspection | IVRS - Inspection :* 1) post ADDRESS 2) HAVE PLANS ON SITE 3) HAVE WORK READY FOR INSP 4) DO NOT USE BRICKS FOR DOBLIES |