Inspection History: FRAMING

Permit Number - T04CM00096

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
04/28/2004 FRAMING Approved IVRS - Inspection :*
04/26/2004 FRAMING Partial Approval IVRS - Inspection :*/ 1) INDIRECT WASTE WATER SOFTNER 2) TIGHTEN H.D. NUT 3) BACKING AT BOTH TUBS 4) BLOCK MECH 5) LOOSE PLATE AT TOILET
04/20/2004 FRAMING Not ready for Inspection IVRS - Inspection 0000*/ 1) SUPPORT FURNACE PLATFORM 2) SOFT WATER DRAIN, DISPOSING OF WATER ? 3) GAS FURNACE FLUE 4) BLOCK ALL MECH 5) KITCHEN SINK COLD SIDE WATER PEX KINKED 6) VIEGA POST LOOSE AT FRONT ENTRY 7) BEAM NOTCHES 1 1/2" = 1/4 OF WIDTH 8) PEX TO BE 12" FROM LIGHT CAN LIVING CEILING 9) FIRE BLOCK AT DRYER DUCT 10) TIGHTEN H.D. NUTS 11) TUB BACKING 12) BANG PLATE PEX SHOWER/TUB 13) LOOSE PLATE AT TOILET 14) DAMAGE WEATHER BARRIER A/C LINE SET EXT. WALL 15) WAHT IS 1/2" DIAMETER PEX IN LAV FOR ? 16) STUD OVERSPAN REAR ENTRY WALL 17) TUB BACK 2ND ? 18) DRAIN WASTE VENT TEST 19) NO RISER ON SERVICE PANEL 20) GAS/POTABLE WATER OK 21) TO MANY ITEMS
04/13/2004 FRAMING Denied IVRS - Inspection 0999*/ 1) ITEMS NOT CORRECTED FROM PREVIOUS INSP
04/09/2004 FRAMING Denied IVRS - Inspection 0999*/ 1) NO TEST ON DWV 2) FIRE BLOCK MISSING AT LAUNDRY 3) MECH BLOCKS MISSING 4) NO GAS PRESSURE TEST 5) FIRE STOP DOUBLE WALL AT HALL BATH 6) TOO MANY ITEMS
03/25/2004 FRAMING Not ready for Inspection IVRS - Inspection 0000*/ 1) NOT READY FOR INSPECTION