Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/28/2004 | FRAMING | Approved | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/26/2004 | FRAMING | Partial Approval | IVRS - Inspection : See detailed listing on site.| 999*/ 1) FIREBLOCK KITCHEN ENTIRE AREA COMMON TO FLOOR JOIST SPACE ENTIRE LENGTH OF GLU 2) DWV TEST TO GO THROUGH ROOF |
|
| 04/22/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) FIRE STOP ALL AREAS OF CONCERN (KITCHEN AREA AT CEILING) 2) INSTALL 10D NAILS HANGERS 3) STRAP ALL ELECTRIC PENETRATIONS THROUGH FRAMING 4) SECURE ELECTRIC AWAY FROM SHARP OBJECTS 5) STRAP ALL PLUMBING 6) REMOVE ALL INSULATION 7) ITEMS NOT CORRECTED 7) STOPPED INSPECTION COMPLETE ALL AND RECALL |
|
| 04/13/2004 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) NO PLANS 2) FIREBLOCK ? KITCHEN AREA ( PASS THROUGH AT CEILINGS) NAIL PROTECT PLB AND ELECTRIC 3) REMOVE INSULATION THROUGHOUT 4) STOPPED INSPECTION 5) REFEE DUE | |
| 04/12/2004 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) WIRE ROMEX INTO EXHAUST FANS 2) INSTALL BANG PLATES ELECTRIC AND PLUMBING THROUGHOUT 3) USE 10D NAILS ALL HANGERS 4) REMOVE INSULATION GARAGE CEILING 5) GARAGE OSB SHEARWALL TO CARRY TO UNDERSIDE OF FLOOR JOISTS 5) FIRE STOP KITCHEN CEILING 6) DWV TEST TO GO THROUGH ROOF 7) INSTALL DOUBLE STUDS ON GIRDER TRUSSES 8) FIRE BLOCKS MISSING GARAGE WALL TO HOUSE 9) INSTALL POSITIVE CONNECTION ALL TRUSSES AT BEARING POINTS 10) STOPPED INSPECTION | |
| 04/07/2004 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) REMOVE ALL INSULATION 2) COMPLETE LATH 3) STOPPED INSPECTION |