Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/20/2004 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) CORRECTIONS HAVE BEEN MADE 2) OK FOR FINAL C OF O |
| 04/15/2004 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) DO NOT SECURE ELEC. CONDUIT TO THE SERVICE ACCESS PANELS ON A/C UNITS. TIGHTEN SEAL TITE FITTINGS. 2) MARK UNIT DATA PLATES WITH PROPER HT KIT INSTALLED AND FUSE ACCORDINGLY. DISCONNECTS HAVE NO FUSES. INSTALL VIBRATION ISOLATORS UNDER UNITS. |
| 04/13/2004 |
MECHANICAL - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) 2:30 PM EQUIPMENT ON ROOF NOT READY FOR INSPECTION |
| 04/09/2004 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0935*/ STRAP ALL FLEX DUCT UP OFF OF CEILING GRID. HOW MANY TIMES DO I NEED TO TELL YOU THIS. EQUIPMENT STILL NOT READY FOR INSP. ON ROOF. PAY A RE-INSPECTION FEE PRIOR TO NEXT INSP. |