Permit: T04CM00084

Parcel: 126130170


Addresses:

4500 E BROADWAY BL


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T04CM00084

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/20/2004 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ 1) CORRECTIONS HAVE BEEN MADE 2) OK FOR FINAL C OF O
04/15/2004 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 1) DO NOT SECURE ELEC. CONDUIT TO THE SERVICE ACCESS PANELS ON A/C UNITS. TIGHTEN SEAL TITE FITTINGS. 2) MARK UNIT DATA PLATES WITH PROPER HT KIT INSTALLED AND FUSE ACCORDINGLY. DISCONNECTS HAVE NO FUSES. INSTALL VIBRATION ISOLATORS UNDER UNITS.
04/13/2004 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) 2:30 PM EQUIPMENT ON ROOF NOT READY FOR INSPECTION
04/09/2004 MECHANICAL - FINAL Denied IVRS - Inspection 0935*/ STRAP ALL FLEX DUCT UP OFF OF CEILING GRID. HOW MANY TIMES DO I NEED TO TELL YOU THIS. EQUIPMENT STILL NOT READY FOR INSP. ON ROOF. PAY A RE-INSPECTION FEE PRIOR TO NEXT INSP.