Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04CM00070
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/12/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
07/08/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) THE SERVICE AT #2 NEEDS A PLASTIC BUSHING WHERE WIRES ENTER REAR OF PANEL 2) USE A ROMEX CONNECTOR WHERE GROUND WIRES ENTER SERVICE BOTTOM OF #1 3) 20 AMP BREAKER IN #2 WILL NOT CLEAR )MARKED SPACE) 4) GFI CIRCUIT IN BATHROOMS #2 NOT ON CIRCUIT ON 5) UNIT #1 KIT GFI NOT TRIPPING, NED 2ND CIRCUIT UNDER GFI 6) WHAT ARE EXTRA WIRES IN PANEL FOR-PROPERLY WIRE NUT |