Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
| Date |
Description |
Inspector |
Results |
Comments |
| 03/11/2004 |
MECHANICAL - HOODS |
|
Approved |
|
| 03/03/2004 |
MECHANICAL - HOODS |
|
Partial Approval |
IVRS - Inspection 0000*/ INSPECTED WELDS ON GREASE DUCT. OK TO PROCEED WITH FIRE WRAP. WRAP SHALL EXTEND ALL THE WAY TO THE TOP OF DUCT AS PER 2000 IMC. HOOD IS HUNG FROM THE BOTTOM CORD OF TRUSS. PROVIDE A LETTER FROM ENGINEER ALLOWING THIS. |