Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/23/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) OK FINAL |
| 03/22/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) HOOD INTER LOCK NOT AS PER PLANS. PLEASE PROVIDE A LETTER FOR INSTALLATION OR INSTALL AS PER PLANS |
| 03/18/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) NO ONE ON SITE TO VERIFY ITEMS LISTED FOR PREVIOUS INSPECTION |
| 03/15/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) SUPPORT M/C CABLE ACROSS TOP OF WALK-IN BOX. 2) AN APPROVED FITTING FOR BOX IS NEEDED. 3) SEAL CONDUIT INTO BOX AS PER CODE 110. 4) VERIFY CONDUCTOR AMPACITY FOR DERATING AS PER 310-15. 5) WHERE IS BOX FOR HOOD MAKE-UP INTERLOCK? 6) WHERE IS ALL EQUIPMENT SO AS TO VERIFY LISTING LABELS. |