Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04CM00065
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/23/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*/ 1) OK FINAL | |
03/22/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) HOOD INTER LOCK NOT AS PER PLANS. PLEASE PROVIDE A LETTER FOR INSTALLATION OR INSTALL AS PER PLANS | |
03/18/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ 1) NO ONE ON SITE TO VERIFY ITEMS LISTED FOR PREVIOUS INSPECTION | |
03/15/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) SUPPORT M/C CABLE ACROSS TOP OF WALK-IN BOX. 2) AN APPROVED FITTING FOR BOX IS NEEDED. 3) SEAL CONDUIT INTO BOX AS PER CODE 110. 4) VERIFY CONDUCTOR AMPACITY FOR DERATING AS PER 310-15. 5) WHERE IS BOX FOR HOOD MAKE-UP INTERLOCK? 6) WHERE IS ALL EQUIPMENT SO AS TO VERIFY LISTING LABELS. |