Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T04CM00047

Parcel: 131010310


Addresses:

4912 E 22ND ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/03/2004 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
03/02/2004 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ PROVIDE SUN SHIELDS OVER CANVAS CONNECTORS. PROVIDE FUSES IN ELEC. DISCONNECTS. PROVIDE CONDENSATE DRAIN LINES. NEED TO SEE DUCT SMOKE DETECTOR POWERED UP AND OPERATIONAL. OK FOR TEMP POWER FOR TESTING. OK FOR TEMP C OF O.