Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T04CM00038
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/23/2004 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
11/02/2004 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) SUPPORT ALL ELECTRICAL J-BOXES, FLEX, LONG DRYWALL SCREWS WITH GAP BETWEEN BOX AND PARTITION NOT ACCEPTABLE |
|
10/29/2004 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/1)PLUG UNUSED OPENINGS IN J-BOXES 2)COMPLETE TERMINATIONS IN J-BOXES & COVERS 3)USE APPROVED EXTENSION RING ON BOXES WITH MORE THAN 1/4" CAP IN DRYWALL |
|
10/27/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*/OK OFFICE AREA EAST | |
10/21/2004 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio |
|
10/20/2004 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/1)SUPPORT J-BOXES AS PER LAST INSP-WRITE -UP. 2)DO NOT USE GRID WIRES INTENDED TO SUPPORT GRID FOR CONDUIT & BOX SUPPORT 3)COMPLETE RANCH CIRCUIT WIRING. NO FLEX OR MC CABLE ON GRID 4)SUPPORT EMT PER NEC,. WITHIN 36" EACH TERM INATION & AT 10' INTERVALS. 5)TIGHTEN CONNECTORS & COUPLINGS |
|
10/18/2004 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :*/ 1) COMPLETE MAKE UP OF LIGHT FIXTURE-2 SCREWS REQUIRED TO FASTEN 2 X 4 FIXTURE TO GRID 2) (2) SUPPORT J-BOXES ABOVE PARTITIONS | |
06/18/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*/ REVISION REQUIRED BY ARCH. FOR CHANGES OF SES OR POWER DIST. SYSTEM. |