Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/15/2004 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
| 07/14/2004 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) SANITARY "T" FITTINGS ARE NOT ALLOWED IN HORIZONTAL DRAINS 2) PROVIDE A 10 FOOT HIGH DWV WATER TTEST ON PLUMBING 3) REVERSE PITCH IN SEWER LINE 4) SEWER PIPE MUST CONTINOUSLY BEAR ON UNDISTURBED SOIL 5) NO PLANS/PERMIT ON SITE 6) STOPPED INSPECTION 7) RESCHEDULE WHEN READY |
|
| 07/08/2004 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) VENT 90 DEGREES NOT PERMITTED IN DRAINAGE 2) SANITARY TEE NOT PERMITTED IN HORIZONTAL DRAINAGE |