Permit: T04CM00031

Parcel: 123091320


Addresses:

2922 E ADAMS ST

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
07/15/2004 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
07/14/2004 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) SANITARY "T" FITTINGS ARE NOT ALLOWED IN HORIZONTAL DRAINS 2) PROVIDE A 10 FOOT HIGH DWV WATER TTEST ON PLUMBING 3) REVERSE PITCH IN SEWER LINE 4) SEWER PIPE MUST CONTINOUSLY BEAR ON UNDISTURBED SOIL 5) NO PLANS/PERMIT ON SITE 6) STOPPED INSPECTION 7) RESCHEDULE WHEN READY
07/08/2004 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) VENT 90 DEGREES NOT PERMITTED IN DRAINAGE 2) SANITARY TEE NOT PERMITTED IN HORIZONTAL DRAINAGE