Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 04/09/2004 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 04/07/2004 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) PROVIDE 1" CLEARANCE FROM COMBUSTIBLES AT WATER HEATER FLUE, ABS SITTING ON TOP OF FLUE |
| 04/02/2004 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) PROVIDE 1" CLEARANCE AT WATER HEATER FLU FROM AB'S AND MOVE ELECTRICAL WIRE AWAY FROM VENT 2) #2, 3, 4 AND 6 FROM EAST INSPECTION NOT DONE # 1 |
| 03/31/2004 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) FIRE BLOCKS MISSING FRONT ENTRY GARAGE 2) MOVE ELECTRICAL WIRES AWAY FROM GUSSETT PLATES 3) NAIL PROTECT ELECTRICAL WITHIN 1 1/4 FROM EDGE OF STUD 4) ROMEX NOT ALLOWED TO BE STAPLED ON IT'S SIDE 5) CHECK FIRE BLOCKS AT STRINGERS 6) SEAL ALL PENETRATIONS INTO 2ND FLOOR AND ATTIC SPACE 7) TO MANY ITEMS STOPPED INSPECTION 8) HAVE TRADES WALK HOUSE BEFORE RECALL |
| 03/30/2004 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) CANCELLED ON SITE BY JOHN |