Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 05/25/2004 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection :* |
| 05/24/2004 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection :*/ SEE VENT FOR WTR HTR. PROVIDE TEST ON ABS. |
| 05/21/2004 |
PLUMBING - INTERMEDIATE |
|
Denied |
1) NO APPROVED PLANS ON SITE. 2) GAS PRESSURE TEST LESS THAN 10 LBS MIN. 3) MUST STRAP DOWN GAS SYSTEM WITH APPROVED STRAPS. 4) HORIZONTAL ABS VENTS MUST BE SECURED EVERY 4'. 5) REMOVE BRASS COUPLING AND GALV. NIPPLE IN GAS LINE. |