Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 04/21/2004 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 04/08/2004 |
FRAMING |
|
Cancelled |
IVRS - Ri canceled |
| 04/07/2004 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) HOLDOWNS NOT INSTALLED 2) OK TO INSULATE |
| 04/05/2004 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) HOLDOWNS MISSING BOLTS AND NOT NAILED 2) ELECTRICAL WIRES RUNNING ON TOP OR SIDE OF GUSSETT PLATES 3) ELECTRICAL FIXTURE BOX FOR BACK PATIO MISSING 4) PROVIDE METAL COLLAR AT WATER HEATER FLUE UPSTAIRS CHASE INTO ATTIC 5) FAN BOXES NOT GROUNDED PROPERLY 6) FIRE BLOCK MECHANICAL CHASE INTO ATTIC 7) PROVIDE 9" UNDER MECHANICAL PLATFORM FOR INSULATION 8) SEAL UNDER TUB ABOVE WATER HEATER PLATFORM |
| 04/01/2004 |
FRAMING |
|
Cancelled |
IVRS - Ri canceled |