Permit: T04CM00016

Parcel: 138242930


Addresses:

1950 W BELLAGIO DR

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
03/04/2004 FRAMING Approved IVRS - Inspection 0000*
03/03/2004 FRAMING Denied IVRS - Inspection 0999*/ 1) PROTECT GAS LINE PER UPC , NUT BY FITTING 2) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACE 3) NAIL OSB SHEAR TO BLOCK 4) HOLDOWN AND ABS
03/01/2004 FRAMING Denied IVRS - Inspection 0399*/ 1) W/H "B" VENT REQURES 1" CLEARANCE TO COMBUSTIBLES 2) DUCT WORK NOT COMPLETE 3) GAS LINE NOT PROPERLY SUPPORTED 4) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACE 5) BACK GROUT TUB FLOOR PENETRATION 6) FIRBLOCK SHEAR BLOCK MISSING BY MASTER SHOWER RENAIL THRU STUCCO 7) SHEAR WALL 8 HOLDOWN BOLTS LOOSE 8) SHEAR WALL 8 REQUIRES 5/8" ANCHOR BOLTS 9) TRUSS BRACE RAT RUN MISSING 10) DWV WATER TEST OK
02/25/2004 FRAMING Not ready for Inspection IVRS - Inspection 0000*/ 1) INTERMEDIATE INSPECTIONS CANNOT BE MADE PRIOR TO LATH BEING INSTALLED AND PASSED