Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 02/19/2004 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000* |
| 02/12/2004 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0935*/ 1) NAIL PROTECT PLUMBING WITHIN 1 1/4" OF WALL SURFACE 2) TRUSSES NOT BRACED PER TRUSS DRAWINGS. SEE ITEM 3 AND 7 FROM 2/10/04 AND 2/11/04 INSPECTIONS. YOU MUST PAY A REINSPECTION FEE PRIOR TO NEXT INSPECTION |
| 02/11/2004 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*1) TRUSS BRACING NOT INSTALLED 2) NAIL PROTECT PLUMBING WITHIN 1 1/4" OF WALL SURFACE 3) TRUSSES NOT CROSS BRACED AT 20 FT O.C. |
| 02/10/2004 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/ 1) SHEAR WALL AT REAR MUST BE NAILED AT 4" ON CENTER AT ENDS AND EDGES 2) NORTH EAST HOLDOWN NAILED TO FULL LENGTH DOUBLE STUDS 3) NAIL PROTECT PLUMBING WITHIN 1 1/4" OF WALL SURFACE 4) NORTH TRUSS NOT CLIPPED ON NORTH EAST CORNER 5) ALL OSB SHEAR WALLS NOT NAILED PER PLAN 6) OSB ROOF PANELS MUST SPAN 3 TRUSSES-TWO BAYS 7) TRUSSES A01M NOT BRACED PER TRUSS DRAWINGS 8) TRUSSED NOT CROSS BRACED AT 20 FEET ON CENTER PER TRUSS CALCS |