Permit: T04CM00010

Parcel: 13510150R

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T04CM00010

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/16/2004 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ OK FOR FINAL C OF O.
03/12/2004 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*/ 1) PROVIDE MIN. 1/8" PER FT. SLOPE ON CONDENSATE DRAIN LINES. 2) ATTACH LABELS TO ELECT. DISCONNECTS. RE-CALL FOR INSP.
02/25/2004 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*/ 1) NEED TO SEE DUCTING FOR BREAK ROOM AND OFFICE 2) NEED TO SEE FINAL DUCT CONNECTIONS ABOVE MAIN RETAIL AREA. SEAL ALL JOINTS. STILL NEED TO SEE DUCT CONNECTIONS IN STORAGE AREA AND ELECTRIC ROOM/JANITORS CLOSET. DO NOT COVER THESE AREAS WITH CEILING TILES