Inspection Status: Approved
Inspection History: SHEET ROCK NAILING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/02/2004 |
SHEET ROCK NAILING |
|
Approved |
IVRS - Inspection 0000* |
| 02/27/2004 |
SHEET ROCK NAILING |
|
Partial Approval |
IVRS - Inspection 0000* NEED TO SEE FRONT COL WRAP |
| 02/26/2004 |
SHEET ROCK NAILING |
|
Partial Approval |
IVRS - Inspection 0000* 3 HR WALL @ EAST END OK TO TAPE. AFTER HOURS INSP |
| 02/18/2004 |
SHEET ROCK NAILING |
|
Partial Approval |
IVRS - Inspection 0000* WEST 3 HR WALL OK |
| 02/17/2004 |
SHEET ROCK NAILING |
|
Partial Approval |
IVRS - Inspection 0000* 1) OK TO SHEET ROCK 1' SIDE OF WALL @ BATHROOM . 2) OK DRYWALL @ DEMISING WALL EAST SIDE. |
| 02/12/2004 |
SHEET ROCK NAILING |
|
Partial Approval |
IVRS - Inspection 0000* OK TO PROCEED WITH TAPING EXCEPT FOR THE FIRE WALLS. |
| 02/11/2004 |
SHEET ROCK NAILING |
|
Partial Approval |
IVRS - Inspection 0000* |
| 02/09/2004 |
SHEET ROCK NAILING |
|
Partial Approval |
IVRS - Inspection 0000* FIRE WALL. 1) PLANS CALL FOR 3 HR FIRE BARRIER @ GRID LINE 5. A FIRE BARRIER MUST EXTEND TO BOTTOM OF DECK. HOW DO YOU PROPOSE RATING THE STEEL BEAM? ENCLOSE OR MONOKOTE? PUL=RLIAS RUN PERPENDICULAR TO STEEL BEAM NOT PARALLEL AS IN PLAN. PARTY WALL DETAIL 2/A8.1 DOES NOT SHOW A TRACE FIRE BARRIER OR FIREWALL. 2) DETAIL FOR 3 HR WALL IS NOT CONSISTANT WITH IBC 705.5 HORIZONTAL CONTINUITY. 3) DETAIL FOR 3 HR WALL NOT CONSISTANT WITHIBC 705.6 FOR VERTICAL CONTINITY. |
| 02/07/2004 |
SHEET ROCK NAILING |
|
Partial Approval |
NORTH-SOUTH DEMISING WALL (OK 1ST LAYER OF 5/8 ON WEST SIDE OF DEMISING WALL |