Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA PLUMBING
Permit Number - T04BU02662
Inspection Description - POOL/SPA PLUMBING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/22/2006 | POOL/SPA PLUMBING | Approved | IVRS - Inspection :* | |
12/08/2005 | POOL/SPA PLUMBING | Partial Approval | IVRS - Inspection :* 6" SCH 40 PVC WATER LINE TO SLIDE - 53 PSI -- OK |
|
12/06/2005 | POOL/SPA PLUMBING | Partial Approval | IVRS - Inspection :*3/4 PVC SCH 80 UNDERGROUND WATER LINE TO H'CAP LIFT PUMP OK EXPOSED PIPING SHALL BE PROTECTED FROM UV RAYS PIPING TO BACKFLOW ASSEMBLY SHALL BE FULL SIZE. BACKFLOW ASSEMBLY REQUIRES A UNION AND CERTIFICATION. |
|
08/17/2005 | POOL/SPA PLUMBING | Partial Approval | IVRS - Inspection :* 1) 50 PSI TEST ON 6" EQUALIZER PIPING AND 50 PSI TEST ON 1" WHEEL CHAIR LIFT LINE OK |
|
08/11/2005 | POOL/SPA PLUMBING | Partial Approval | IVRS - Inspection :* 1) ALL PIPING TO SPRAY COURT AND POOL 50 PSI TEST OK 2) 6" SLIDE SUPPLY STUBBED TO POINT ON PLAN PER INITAL 3) 1" H20 TO ADDED WHEEL CHAIR LIFT 50 PSI TEST OK-PENDING PROPER BACKFLOW PROTECTION 4) 1 NEED TO SEE 6" SLIDE CONTINUATION AND MECH PODS COMPLETION |
|
08/10/2005 | POOL/SPA PLUMBING | Cancelled | IVRS - RI canceled | |
07/14/2005 | POOL/SPA PLUMBING | Partial Approval | IVRS - Inspection :* 1 1/2" TO (4) GROUND SPRAYS 35 & P SI TEST TO SOUTHEAST CORNER OF POOL OK | |
07/08/2005 | POOL/SPA PLUMBING | Partial Approval | IVRS - Inspection :* 50 PSI TEST ON 2 1/2" BALANCE LINE REPAIR OK | |
07/07/2005 | POOL/SPA PLUMBING | Partial Approval | IVRS - Inspection :* (4) 1 1/2 VORTEX LINES COMPLETED 50 PSI TEST OK. 10" GUTTER DOWN TO 8'' TO (3) GUTTER SUCTIONS. 50 PSI TEST OK. 2 1/2 BALANCE LINE TO 3" FROM POOL 50 PSI TEST OK. 2 1/2 WALL RETURN TO ( 4) 1 1/2 INLETS 50 PSI TEST OK. 1) NEED TO REPAIR LEAK ON 2 1/2 BALANCE LINE 2' FROM EQUIPMENT ROOM NORTH WAL. 2" FILL LINE TO TERMINATION AT POOL 50 PSI TEST OK | |
06/15/2005 | POOL/SPA PLUMBING | Partial Approval | IVRS - Inspection :* 1) 50 PLUS AIR PRESSURE TEST IS OK. FOR UNDERGROUND POOL PIPING IS OK AS INITIALED ON PLAN. | |
06/09/2005 | POOL/SPA PLUMBING | Partial Approval | IVRS - Inspection :* 1) 50 PLUS PSI WATER TEST PER HIGHLIGHTED INITALED PLAN IN TRAILER ON ZERO ENTRY POOL |
|
06/08/2005 | POOL/SPA PLUMBING | Not ready for Inspection | IVRS - Inspection :* | |
06/02/2005 | POOL/SPA PLUMBING | Partial Approval | IVRS - Inspection :* / ALL UNDERGROUND PIPING FROM MECH ROOM PAGE PP1.1 TO 10' TOWARD POOL 50 PSI TEST OK PER APPROVED PLAN PP1.1 |