Permit: T04BU02573

Parcel: 124172340


Addresses:

1001 E 17TH ST


Inspection Status: Approved

Inspection History: POOL/SPA GAS

Permit Number - T04BU02573

Inspection Description - POOL/SPA GAS

Inspection Status - Approved

Date Description Inspector Results Comments
02/10/2005 POOL/SPA GAS Approved IVRS - Inspection :* 1) GAS PRESSURE TEST IS OK. 2) GAS SHUT OFF VALVES OK 3) FINAL CONNECTION TO POOL HTRS OK. 4) OK TO BACKFILL TRENCH.
02/09/2005 POOL/SPA GAS Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) SHALL PROVIDE TAPE AND APPROVED TAPE PRIMER ON UNDERGROUND JOINTS AND ALL WRENCH MARKS. THERE IS SOME AREAS THAT DO NOT HAVE TAPE. CHECK YOUR WORK PRIOR TO NEXT INSPECTION. 2) DO NOT COVER.
02/07/2005 POOL/SPA GAS Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) GAS LINE REQUIRED MIN 12" OF COVER . 2) SHALL PROVIDE YELLOW TAPE PRIMER THEN APPLY 10 MI? TAPE TO ALL UNDERGROUND FITTINGS AND WRENCH MACKS. 3) RE TEST THE SYSTEM.
02/03/2005 POOL/SPA GAS Denied 1) SHALL EXPOSE GAS LINE UNDERGROUND 2) GAS PRESSURE TEST IS @ LBS 10 LBS MIN @ TIME OF INSPECTION