Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/17/2005 | FIRE SPKLR - FINAL | Approved | ||
| 03/14/2005 | FIRE SPKLR - FINAL | Not ready for Inspection | Need as builts. | |
| 03/10/2005 | FIRE SPKLR - FINAL | Not ready for Inspection | Unit 100 - painted head storage room 101 - head to far off wall 9' 1" need to be 8' max. 102 - head to far off wall 9' 2" need to be 8' max 103 - head guard needed under stairs |