Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA FINAL/BARRIER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/02/2005 | POOL/SPA FINAL/BARRIER | Approved | IVRS - Inspection :* | |
| 11/16/2004 | POOL/SPA FINAL/BARRIER | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) EXISTING ELECTRIC PANEL APPEARS TO BE UNDER SIZED FOR ALL LOADS CONSIDERED INCLUDING POOL; HAVE ELECTRICIAN CALC LOADS TO SEE IF UPGRADE IS NECESSARY 2) FILL UNUSED OPENING ELECTRIC PANEL AND LABEL POOL CIRCUIT/IN PANEL BOX 3) PLAN SHOWS NO WINDOW IN HOUSE WALL, INCLUDING ENCLOSURE (RE-SUBMIT REVISED PLAN FOR APPROVAL) 4) MAXIMUM 4" OPENING ALLOWED UNDER POOL FENCE 5) NO OPENINGS LARGER THAN 4" SPHERE WILL PASS THROUGH ALLOWED IN ENCLOSURE (RE:GATE) 6) GATE LATCH TO BE 54' ABOVE WALKING SURFACE |