Permit: T04BU02199

Parcel: 141171420


Addresses:

8461 S BURIEN RD


Inspection Status: Approved

Inspection History: POOL/SPA ELECTRIC

Permit Number - T04BU02199

Inspection Description - POOL/SPA ELECTRIC

Inspection Status - Approved

Date Description Inspector Results Comments
04/07/2005 POOL/SPA ELECTRIC Approved IVRS - Inspection :*
1) EGRESS THRU BATHROOM WINDOW
01/27/2005 POOL/SPA ELECTRIC Not ready for Inspection IVRS - Inspection :*
1 FRM LAST INSP CONDUIT FROM LIGHT CANS WAS ONLY 10' LONG, NO INSP FROM J-BOX TO THAT 10', J-BOX WASN'T INSTALLED AT LAST INSP
2 WINDOWS INSIDE ENCLOSURE TO BE PINNED, NOT TO OPEN MORE THAN 4", DOESN'T APPLY TO EGRESS WINDOWS, THEY CANNOT BE IN THE ENCLOSURE UNDER OLD CODE. NEW CODE ADOPTED 9-7-04
3 SPACE UNDER BARRIER NOT TO EXCEED 4"
4 GATES 4' LATCH REQUIREMENT 50" ABOVE FOOT HOLD. SEE #5 SEC 3.17 POOL CODE
5 YOU HAVE VALVES DOWNSTREAM OF HRT T.3.P VALVE REQ
6 REPLACE VACUUM BREAKER ON HOSE BIB
10/08/2004 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :* NOTE: 1) HOME RUN ELECT TO SERV NOT INSTALLED 2) J BOX NOT INSTALLED FOR LIGHT CANS CONDUIT RUN 10 ' FROM POOL, NO FARTHER, ? J-BOX. 3) DETAIL ?/52 US? BARS ARE EXTRA. 4) POOL HTRS PLEASE HAVE PROOF THAT T & PS AREN'T NEEDED OR INSTALL THEM PER MY SUPV.