Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA ELECTRIC
Permit Number - T04BU02199
Inspection Description - POOL/SPA ELECTRIC
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/07/2005 | POOL/SPA ELECTRIC | Approved | IVRS - Inspection :* 1) EGRESS THRU BATHROOM WINDOW |
|
01/27/2005 | POOL/SPA ELECTRIC | Not ready for Inspection | IVRS - Inspection :* 1 FRM LAST INSP CONDUIT FROM LIGHT CANS WAS ONLY 10' LONG, NO INSP FROM J-BOX TO THAT 10', J-BOX WASN'T INSTALLED AT LAST INSP 2 WINDOWS INSIDE ENCLOSURE TO BE PINNED, NOT TO OPEN MORE THAN 4", DOESN'T APPLY TO EGRESS WINDOWS, THEY CANNOT BE IN THE ENCLOSURE UNDER OLD CODE. NEW CODE ADOPTED 9-7-04 3 SPACE UNDER BARRIER NOT TO EXCEED 4" 4 GATES 4' LATCH REQUIREMENT 50" ABOVE FOOT HOLD. SEE #5 SEC 3.17 POOL CODE 5 YOU HAVE VALVES DOWNSTREAM OF HRT T.3.P VALVE REQ 6 REPLACE VACUUM BREAKER ON HOSE BIB |
|
10/08/2004 | POOL/SPA ELECTRIC | Partial Approval | IVRS - Inspection :* NOTE: 1) HOME RUN ELECT TO SERV NOT INSTALLED 2) J BOX NOT INSTALLED FOR LIGHT CANS CONDUIT RUN 10 ' FROM POOL, NO FARTHER, ? J-BOX. 3) DETAIL ?/52 US? BARS ARE EXTRA. 4) POOL HTRS PLEASE HAVE PROOF THAT T & PS AREN'T NEEDED OR INSTALL THEM PER MY SUPV. |