Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T04BU02117

Parcel: 141172490

Inspection Status: Not ready for Inspection

Inspection History: POOL/SPA PLUMBING

Date Description Inspector Results Comments
09/30/2004 POOL/SPA PLUMBING Not ready for Inspection IVRS - Inspection :*/ 1) SPA LIGHT, BOND WIRE NOT COVERED WITH SEALANT, CU. WIRE IS EXPOSED 2) UNCOVER ELECTRIC GALVANIZED PIPE NOT APPROVED FOR WET NICHE TO J-BOX PLASTIC, OR BRASS 3) NEED BOX EXTENSION AT GFCI RECEPT, REMOVE COVER FROM COVER PLATE OR USE CORRECT PLATE 4) NEED ANTI-SYPON DEVICE AT HOSE BIB 5) WHY IS THERE A 2 POLE 20/20 AMP CIRCUIT LABELLED POOL HEATER WHEN THE HTR IS GAS? 6) HTR. SPEC BOOK REF T&P VALVE NOTE: NEW POOL CODE GOES INTO EFFECT 9/8/04. CHANGES IN BARRIER/ENCLOSURE REQ. ANY PERMIT DATED AFTER 9/8/04-NOT THIS POOL
09/03/2004 POOL/SPA PLUMBING Partial Approval IVRS - Inspection :*/ 1) HOME RUNS NOT COMPLETED, OK TO COVER GAS LINE 2) OK TO COVER H20 LINES 3) POOL LIGHT CONDUIT FROM POOL SHELL TO J-BOX NOT INSTALLED 4) CANNOT CONNECT CU. H20 FITTING TO GALV. PIPE. INSTALLL VACCUM BREAKER 5) NEED SPEC BOOK ON HTR. 6) OK TO GUNITE