Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T04BU02117

Parcel: 141172490

Inspection Status: Not ready for Inspection

Inspection History: POOL/SPA PLUMBING

Permit Number - T04BU02117

Inspection Description - POOL/SPA PLUMBING

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
09/30/2004 POOL/SPA PLUMBING Not ready for Inspection IVRS - Inspection :*/ 1) SPA LIGHT, BOND WIRE NOT COVERED WITH SEALANT, CU. WIRE IS EXPOSED 2) UNCOVER ELECTRIC GALVANIZED PIPE NOT APPROVED FOR WET NICHE TO J-BOX PLASTIC, OR BRASS 3) NEED BOX EXTENSION AT GFCI RECEPT, REMOVE COVER FROM COVER PLATE OR USE CORRECT PLATE 4) NEED ANTI-SYPON DEVICE AT HOSE BIB 5) WHY IS THERE A 2 POLE 20/20 AMP CIRCUIT LABELLED POOL HEATER WHEN THE HTR IS GAS? 6) HTR. SPEC BOOK REF T&P VALVE NOTE: NEW POOL CODE GOES INTO EFFECT 9/8/04. CHANGES IN BARRIER/ENCLOSURE REQ. ANY PERMIT DATED AFTER 9/8/04-NOT THIS POOL
09/03/2004 POOL/SPA PLUMBING Partial Approval IVRS - Inspection :*/ 1) HOME RUNS NOT COMPLETED, OK TO COVER GAS LINE 2) OK TO COVER H20 LINES 3) POOL LIGHT CONDUIT FROM POOL SHELL TO J-BOX NOT INSTALLED 4) CANNOT CONNECT CU. H20 FITTING TO GALV. PIPE. INSTALLL VACCUM BREAKER 5) NEED SPEC BOOK ON HTR. 6) OK TO GUNITE