Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T04BU02048
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/14/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)NEC-99 305 TEMPORARY WIRING FOR CONSTRUCTION AND FOR TEMPORARY TRAILER "FLEXIBLE CORDS AND CABLES SHALL BE PROTECTED FROM ACCIDENTIAL DAMAGE" STRINGING CABLE ALONG FENCE IS HAZARDOUS DUE TO MOVING FENCE, AND LAYING IT ON FLOOR DOES NOT PROVIDE CABLE ANY PROTECTION. 2)MAIN CB ON TRAILER NEEDS CLIP DOWN 348-16G NEC 3)NEED SCREWS ON TRAILER DEAD FRONT COVER |