Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA PLUMBING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/08/2004 | POOL/SPA PLUMBING | Approved | IVRS - Inspection :* | |
| 08/31/2004 | POOL/SPA PLUMBING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) SEE ITEMS FROM PRIOR INSPECTION 2) DO NOT COVER PLUBMING ELECTRIC FROM PUM TO FRONT OF HOUSE |
|
| 08/27/2004 | POOL/SPA PLUMBING | Denied | IVRS - Inspection :WINDOWS DO NOT NEED TO COMPLY UNTIL FINAL INSPECTION BUT ALL OTHER ITEMS EXCEPT ITEMS 3 & 4 OF 8-18-04 INSPECTION HAVE NOT BEEN COMPLIED WITH NEXT FAILURE MAY BE CHARGED A RE-FEE |
|
| 08/18/2004 | POOL/SPA PLUMBING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) ELECTRIC PLASTIC CONDUIT MUST BE 18" BELOW GRADE 2) WINDOWS WITHIN 5 FEET OF POOL MUST BE SAFETY GLAZED 3) REINFORCING STEEL IS NOT PER PLAN IN SURCHARGE AREA OF HOUSE 4) DETAIL Q OF PLAN NOT COMPLIED WITH AT LIGHT 5) REBAR TOO FAR APART ON NORTH WALL 6) 1 1/2" CLEARANCE REQUIRED BETWEEN PLUMBING AND REBAR 7) BLACK PIPE NIPPLE NOT ALLOWED IN AUTOFILL WATER SYSTEM POTABLE SIDE 8) WATER LINE MUST BE 12" BELOW GRADE |