Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/17/2004 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection :* | |
| 08/12/2004 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ FINISH ITEMS 2 & 4 OF PREVIOUS INSP. |
|
| 08/09/2004 | ELECTRIC - TEMPORARY SERVICE | Not ready for Inspection | IVRS - Inspection :*/ 1) ADDRESS LABEL TO BE PERMANENT METAL 2) A BOND BUSHING IS NEEDED FOR RISER 250.72 3) PROPERLY SUPPORT PVC CONDUIT UNDER TRAILER 4) WHERE IS TRAILER GROUNDING ELECTRODE SYSTEM CONNECTED TO ? WHERE IS 2ND GROUND ROD ? |