Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T04BU01736

Parcel: 11611005H


Addresses:

2800 W BROADWAY BL


Inspection Status: Approved

Inspection History: POOL/SPA GAS

Permit Number - T04BU01736

Inspection Description - POOL/SPA GAS

Inspection Status - Approved

Date Description Inspector Results Comments
03/23/2005 POOL/SPA GAS Approved IVRS - Inspection :* 1) APPROVED PLAN ON SITE. CONTRACTOR TO REDLINE GAS ROUTING CHANGE
03/22/2005 POOL/SPA GAS Not ready for Inspection IVRS - Inspection :* 1) JOBSITE TRAILER HAS BEEN REMOVED. UNABLE TO LOCATE PLAN OR PERMIT. 2) FEMALE PVC THREADED FITTINGS ARE PROHIBITED ON WATER PIPING. 3) PVC WATER PIPING EXPOSED EXTERIOR LOCATION NOT PERMITTED ( ALSO IT IS LEAKING)
02/16/2005 POOL/SPA GAS Not ready for Inspection IVRS - Inspection :* NOT READY
11/24/2004 POOL/SPA GAS Partial Approval 1)WILL REQUIRE REVISED APPROVED PLAN SHOWING METER RELOCATE TO POOL EQUIPMENT AREA; AND NEW ROUTING OF BBQ GAS-REDLINES ON SITE. OK TO COVER
11/23/2004 POOL/SPA GAS Not ready for Inspection IVRS - Inspection :*/1)BBQ GAS NOT ON PLAN - REMEMBER, IF 3/4" PLASTIC GAS IS APPROVED FOR BBQ ALL UNSLEEVED GAS TO BE SHADED AND BEDDED IN SAND. 2)REVISE PLAN FOR NEW LAYOUT. INCLUDE GAS ISOMETRIC SHOWING TOTAL BTU AND DEVELOPED LENGTH
11/22/2004 POOL/SPA GAS Not ready for Inspection IVRS - Inspection :*