Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA ELECTRIC
Permit Number - T04BU01736
Inspection Description - POOL/SPA ELECTRIC
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/08/2005 | POOL/SPA ELECTRIC | Approved | IVRS - Inspection :* 1) INSPECTION NOT CALLED IN PRIOR TO COOL DECKING, NEED TO VERIFY ALL METAL DEVICES, LADDERS, E??UTIONS, GROUNDED. 2) OK BASKETBALL HOOP GROUNDED PER CONTINUITY TEST LADDERS. HAND RAILS, TEST BY HEATH KENYON MAINT. SUPERVISOR WITNESSES BY DAN SANTA CRUZ | |
| 02/07/2005 | POOL/SPA ELECTRIC | Partial Approval | IVRS - Inspection :* GROUNDING OF BASKETBALL FRAME NOT VISIBLE ANY METAL POLES, EQUIPMENT, ETC WITHIN 5' AT THE POOLS EDGE MUST BE GROUNDED | |
| 09/13/2004 | POOL/SPA ELECTRIC | Partial Approval | IVRS - Inspection :*/ 1) OK REBAR AND LIGHT FIXTURE GROUNDING POOL AND SPA 2) RECONNECT INSPECTION FOR ? AND LADDER BONDING BEFORE COOL DECKING 2) OK TO GUNITE |