Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA PLUMBING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/30/2004 | POOL/SPA PLUMBING | Approved | IVRS - Inspection :*/1)GAS PRESSURE TEST IS OK 2)GAS SHUT OFF VALVES FOR ALL POOL EQUIPMENT IS OK | |
| 10/22/2004 | POOL/SPA PLUMBING | Partial Approval | 1) AIR AND WATER PRESSURE TEST IS OK. 30 POUNDS MINIMUM FOR UNDERGROUND SUPPLY AND RETURN LINES FOR ADULT POOL AND ACTIVE POOL AND FOUNTAIN 2) OK TO BACKFILL TRENCH |
|
| 09/28/2004 | POOL/SPA PLUMBING | Partial Approval | 1) ROUGH PLBS. FOR LAP POOL AND SPA #3 ARE OK. 2) WATER & AIR TEST 30 LBS OK 3) ACTIVITY POOL, ADULT POOL AND SPA # ? AND 2 WATER & AIR TEST 30 LBS OK AS NOTED ON PLAN. 4) OK TO BACKFILL TRENCHES. | |
| 09/24/2004 | POOL/SPA PLUMBING | Not ready for Inspection | IVRS - Inspection :*1)NOT READY FOR INSPECTION | |
| 08/31/2004 | POOL/SPA PLUMBING | Partial Approval | IVRS - Inspection :*/ 1) WATER AND AIR PRESSURE TEST OF 30 POUNDS OK 2) THIS INSPECTION IS FOR ADULT POOL, ACTIVE POOL, SPA #1 AND SPA #2 ONLY 3) NOTE: SHALL PROVIDE CLEAN BACKFILL FOR ALL PLBG TRENCHES 4) OK FOR GUNITE | |
| 08/25/2004 | POOL/SPA PLUMBING | Partial Approval | IVRS - Inspection :*/ 1) PRESSURE TEST OF 30 POUNDS OK 2) ROUGH PLUMBING FOR SPA #4 AND 5 ARE OK 3) OK FOR GUNITE |