Permit: T04BU01649

Parcel: 11628001E

Inspection Status: Approved

Inspection History: POOL/SPA PLUMBING

Date Description Inspector Results Comments
12/30/2004 POOL/SPA PLUMBING Approved IVRS - Inspection :*/1)GAS PRESSURE TEST IS OK 2)GAS SHUT OFF VALVES FOR ALL POOL EQUIPMENT IS OK
10/22/2004 POOL/SPA PLUMBING Partial Approval 1) AIR AND WATER PRESSURE TEST IS OK. 30 POUNDS MINIMUM FOR UNDERGROUND SUPPLY AND RETURN LINES FOR ADULT POOL AND ACTIVE POOL AND FOUNTAIN
2) OK TO BACKFILL TRENCH
09/28/2004 POOL/SPA PLUMBING Partial Approval 1) ROUGH PLBS. FOR LAP POOL AND SPA #3 ARE OK. 2) WATER & AIR TEST 30 LBS OK 3) ACTIVITY POOL, ADULT POOL AND SPA # ? AND 2 WATER & AIR TEST 30 LBS OK AS NOTED ON PLAN. 4) OK TO BACKFILL TRENCHES.
09/24/2004 POOL/SPA PLUMBING Not ready for Inspection IVRS - Inspection :*1)NOT READY FOR INSPECTION
08/31/2004 POOL/SPA PLUMBING Partial Approval IVRS - Inspection :*/ 1) WATER AND AIR PRESSURE TEST OF 30 POUNDS OK 2) THIS INSPECTION IS FOR ADULT POOL, ACTIVE POOL, SPA #1 AND SPA #2 ONLY 3) NOTE: SHALL PROVIDE CLEAN BACKFILL FOR ALL PLBG TRENCHES 4) OK FOR GUNITE
08/25/2004 POOL/SPA PLUMBING Partial Approval IVRS - Inspection :*/ 1) PRESSURE TEST OF 30 POUNDS OK 2) ROUGH PLUMBING FOR SPA #4 AND 5 ARE OK 3) OK FOR GUNITE