Permit: T04BU01597

Parcel: 13342001C


Addresses:

6795 E CALLE LA PAZ

Inspection Status: Approved

Inspection History: POOL/SPA ELECTRIC

Date Description Inspector Results Comments
03/24/2005 POOL/SPA ELECTRIC Approved IVRS - Inspection :* OK POOL ELECTRIC
03/23/2005 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :* 1) 680-20 (6) (2) PUTTING COMPOUND IS NEEDED FOR CORD JACKET AT FORMAIN SHELL. 2) SPA SWITCH TO BE WEATHERPROOF OR COVER.
02/11/2005 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :* OK PRE DECK BONDING
12/23/2004 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
1) OK PVC CONDUITS-OK TO GUNITE
2) RECALL FOR PRE DECK INSPECTION
12/16/2004 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
1) FINISH #1 PREVIOUS INSPECTION
2) MEET WITH CONTRACTOR TO DISCUSS WORK
12/10/2004 POOL/SPA ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO MORE THAN 360 DEGREE IN A CONDUIT RUN
2) USE APPROVED ELECTRICAL FITTINGS NOT WATER PIPE
3) VERIFY LISTING OF ELECTRICAL PVC GLUE
4) NEED TO SEE DECK ESCUTIONS
5) NEED TO SEE PRE DECK BONDING
6) MOTOR AND PUMP AREA COVERED WITH OUT INSPECTION