Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA ELECTRIC
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/21/2005 | POOL/SPA ELECTRIC | Approved | IVRS - Inspection :*OK POOL | |
| 11/15/2005 | POOL/SPA ELECTRIC | Partial Approval | IVRS - Inspection :*PLEASE REMOVE LIGHTS FOR SHELL INSPECTION WHERE IS EMERGENCY SUT OFF AND SINAGE? DO NOT FILL POOL WITHOUT INSPECTION. |
|
| 11/14/2005 | POOL/SPA ELECTRIC | Partial Approval | IVRS - Inspection :* 1) PLEASE FINISH ITEMS #1, 3, 4 AND 8 AS DISCUSSED |
|
| 11/12/2005 | POOL/SPA ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. RECEPTACLE COVER TO BE WEATHERPROOF WHETHER PLUGGED IN OR NOT (406.8) 2. FINISH ITEMS #1, 4 AND 8 OF PREVIOUS INSPECTION |
|
| 11/07/2005 | POOL/SPA ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* BOND POOL JUNCTION BOX WITH # 8 BOND WE HAVE CONDUCTOR ?? FILL IN JUNCTION BOX ALSO BOND BOX WITH GROUNDING EQUIPMENT CONDUCTOR PLEASE VERIFY LISTING LABEL FOR MINI MAX NT WE HAVE MULTIPLE TERMINATIONS AT GROUND LUG. SHEET METAL SCREW NOT FOR GROUNDING 110.3,110.14, 250.8 LABEL PANEL ON OUTSIDE COVER PLEASE VERIFY GROUNDING ELECTRODE SYSTEM-2 GROUND RODS A MAIN DISCONNECTING MEANS IS NEEDED 225.31 PROPERLY INSTALL REDUCING WASHERS |
|
| 11/03/2005 | POOL/SPA ELECTRIC | Cancelled | IVRS - RI canceled | |
| 10/24/2005 | POOL/SPA ELECTRIC | Partial Approval | IVRS - Inspection :*A BOND MAY BE NEEDED FOR FENCE IF WITHIN 5' OF WATER. OK COOL DECK | |
| 07/14/2005 | POOL/SPA ELECTRIC | Partial Approval | IVRS - Inspection :* OK BONDING ON POOL SHELL. 1) PLEASE RE CALL FOR COOL DECK AND ES??? |