Permit: T04BU01527


Addresses:

2779 N NERUDA LN


Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T04BU01527

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
07/12/2004 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
07/07/2004 ELECTRIC - CABLE DROP Denied CONVERSATION OVER THE PHONE WITH R. HOLLANDER REQUESTED THAT THE APPROVALS FOR TEMP SERVICE AND CABLE DROP DATED 7/7/04 BE CHANGED TO DENIED
07/06/2004 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*/ 1) FILL UNUSED OPENINGS IN BACK OF PANEL 2) USE CORRECT SIZED REDUCING WASHERS AND TIGHTEN FITTING 3) LABEL BREAKERS 4) SUPPORT RISER WITHIN 3' OF SERVICE 5) FITTING TO TRAILER PANEL BROKEN 6) NEED GROUNDING ELECTRODE SYSTEM FOR ? 7) LARGER THAN #8 IN RACEWAY TO BE STRANDED 8) A MAIN BREAKER IS NEEDED FOR TRAILER AND TIGHTEN TERMINATIONS
07/01/2004 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
The inspector was unable to locate the job.| 945*