Inspection Status: Approved
Inspection History: POOL/SPA ELECTRIC
| Date |
Description |
Inspector |
Results |
Comments |
| 07/12/2004 |
POOL/SPA ELECTRIC |
|
Approved |
IVRS - Inspection :* |
| 06/14/2004 |
POOL/SPA ELECTRIC |
|
Partial Approval |
IVRS - Inspection :*/ 1) POOL GAS LINE MISSING TRACER WIRE 2) ALL BUT 10 FEET OF POOL GAS LINE COVERED WITHOUT INSPECTION-EXPOSE 3) NO USABLE MANUFACTURER LABEL OR UPC LABEL ON GAS LINE 4) POOL HEATER NOT BONDED 5) PUMP NOT BONDED OR WIRED 6) PROVIDE POOL HEATER INSTALLATION MANUAL 7) BONDS AND CONDUIT PROPERLY INSTALLED |