Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/14/2004 | FIRE SPKLR - FINAL | Approved | ||
| 07/07/2004 | FIRE SPKLR - FINAL | Cancelled | IVRS - Ri canceled | |
| 07/06/2004 | FIRE SPKLR - FINAL | Not ready for Inspection | 1. Need electric power to waterflow alarm. 2. Needs lock & chain for main control valve supervision. 3. Needs signs and spare sprinkler head box. |