Inspection History Details
Inspection Status: Partial Approval
Inspection History: MODULAR - ELECTRIC INSPECTION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/15/2004 | MODULAR - ELECTRIC INSPECTION | Partial Approval | IVRS - Inspection :* | |
| 06/08/2004 | MODULAR - ELECTRIC INSPECTION | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) 'SB' CABLE NOT ALLOWED FOR PRIMARY FEEDER CABLE. 2) ANTIOXIDE COMPOUND NEEDED ON ALL ALUM CONDUCTORS. 3) PROTECT SOB FEEDER TO PANEL FOR TRACKER. 4) PROVIDE GROUNDING ELECTRODE SYSTEM FOR TRAILER. 5) THIS INSTALLATION TO MEET REQUIREMENTS OF ART. 305. |
|
| 06/03/2004 | MODULAR - ELECTRIC INSPECTION | Not ready for Inspection | IVRS - Inspection :*/ 1) RISER TO BE SCHEDULE 80. 2) GROUNDING ELECTRODE SYSTEM NOT CONNECTED. 3) TRAILER NOT CONNECTED. |