Inspection History Details
Inspection Status: Denied
Inspection History: POOL/SPA FINAL/BARRIER
Permit Number - T04BU01130
Inspection Description - POOL/SPA FINAL/BARRIER
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/22/2004 | POOL/SPA FINAL/BARRIER | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) MUST COMPLETE ITEMS #1 AND #3 ABOVE REFEE DUE |
|
07/13/2004 | POOL/SPA FINAL/BARRIER | Partial Approval | IVRS - Inspection :*/ 1) MUST UNCOVER ALL ELECTRIC UNDERGROUND FROM MAIN PANEL TO ? SUB PANEL FOR VERIFICATION OF MATERIAL AND DEPTH 2) OK TO PLASTER AND FILL WITH H20 3) WHEN USING PROPANE TANK MUST HAVE TUCSON FIRE DEPT PERMIT AND APPROVAL FIRST 4) COMPLETE ALL AND RECALL | |
07/09/2004 | POOL/SPA FINAL/BARRIER | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) PAGE 17 POOL HEATER MANUAL REQUIRES SEDIMENT TRAP INSTALLED GAS LINES 2) PAGE 27 SHOWS INSTALLATION OF PRESSURE RELIEF VALVE 3) MUST UNCOVER ELECTRIC FROM MAIN PANEL TO POOL EQUIPMENT |
|
07/07/2004 | POOL/SPA FINAL/BARRIER | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) ALL GATES TO BE SELF-CLOSING, SELF LATCHING IN POOL ENCLOSURE 2) CANNOT HAVE ANYTHING CLIMBABLE OUTSIDE OF ENCLOSURE WITHIN 48" RADIUS OF TOP OF ENCLOSURE 3) INSTALL ANTI-SIPHON HOSE BIBS 4) INSTALL HEATER PTR VALVE OR SUPPLY MANUFACTURER LISTING NOT REQUIRING IT 5) NEED VERIFICATION OF 8035 APPROVAL 6) UNABLE TO LOCATE PLANS/PERMIT 7) STOPPED INSPECTION |